Hluav taws kub twj tso kua mis tswj txee

Xa kev nug
Hluav taws kub twj tso kua mis tswj txee
Paub meej
Rated khiav hauj lwm voltage: AC380V/50Hz Peb-theem plaub-hlau
Tswj lub cev muaj zog: 15KW-160KW (tus qauv fais fab rau lub hnub qub-delta adapter)
Txoj kev pib: Lub hnub qub-delta (Y / Δ) kauj ruam- nqis pib hloov pauv tsis siv neeg
Lub sij hawm pib: 3-15 vib nas this (adjustable nrog maub los)
Pib tam sim no: Ib qho -peb peb ntawm tag nrho-voltage start- nce kom txo tau qhov cuam tshuam ntawm daim phiaj hluav taws xob.
Kev faib tawm yam khoom
Lub zog Switchgear
Share to
Hauj lwm lawm

Hluav taws kub twj tso kua mis tswj txee cov khoom siv phau ntawv (hnub qub-delta pib, nrog cov neeg kho tshuab thaum muaj xwm ceev phau ntawv tswj)

 

Product Overview

 

Qhov no series ntawm hluav taws twj tso kua mis tswj txee yogtshwj xeeb hluav taws tiv thaiv hluav taws xob tswj cov cuab yeej, nruj me ntsis tsim thiab tsim nyob rau hauv raws li "GB 16806-2006 Fire Linkage Control System" thiab "GB 50974-2014 Technical Specification for Fire Water Supply and Fire Hydrant System". Lawv tau tsim tshwj xeeb rau kev siv cov twj tua hluav taws, cov twj tso kua mis, cov twj tso kua mis siab, thiab lwm yam twj tso kua mis. Cov cuab yeej siv taulub hnub qub-delta txo-voltage start method, yog txawm peem rau nrog ib tug tshwj xeeb kev txawj ntse hluav taws xob maub los, thiab los txheem nrog ob qho tib sihluav taws xob phau ntawv thiab txhua yam xwm txheej ceev phau ntawv twj tso kua mis pib ua haujlwm. Nws muaj ntau yam kev ua haujlwm suav nrog kev sib txuas tsis siv neeg, kev tswj chaw taws teeb, kev tiv thaiv kev ua txhaum, kev saib xyuas xwm txheej, thiab kev kub ntxhov yuam kom pib, ua rau nws yog ib qho tseem ceeb tswj cov cuab yeej siv hluav taws xob hauv tsev.

 

Cov khoom siv dav siv hauv ntau yam kev tiv thaiv hluav taws xob engineering xws li cov chaw lag luam, cov zej zog hauv zej zog, cov chaw tsim khoom, cov tsev ua haujlwm, thiab cov vaj tsev pej xeem. Lawv txhawb ntau hom kev tswj hwm, suav nrog ib qho - ntawm - ib qho chaw tos txais thiab ob - ntawm - ib qho chaw tos txais, thiab muaj kev ruaj ntseg hauv kev ua haujlwm, nrog kev tiv thaiv tiav thiab ua raws li cov qauv kev lees paub kev tiv thaiv hluav taws. Lawv tuaj yeem ua kom ntseeg tau tias qhov pib thiab tso tseg ntawm cov twj tua hluav taws nyob rau hauv cov xwm txheej hluav taws kub thiab ua tau raws li qhov yuav tsum tau ua rau hluav taws kub ceev dej.

 

Lub ntsiab lus qauv

 

XF - KB - Y/△ - □

  • XF: Cov khoom siv tua hluav taws
  • KB: Tswj txee
  • Y/△: Lub hnub qub-delta txo voltage pib txoj kev
  • □: Tau tshaj lub twj tso kua mis dej (15KW / 22KW / 30KW / 45KW / 55KW / 75KW, thiab lwm yam)
XFXL

 

Main Technical Parameters

 

Serial Number

Technology Projects

Parameter Indicators

1

Rated ua haujlwm voltage

AC380V/50Hz Peb-theem plaub-hlau

2

Tswj lub cev muaj zog

15KW-160KW (tus qauv fais fab rau lub hnub qub-delta adapter)

3

Txoj kev pib

Lub hnub qub-delta (Y/Δ) kauj ruam- nqis pib hloov pauv tsis siv neeg

4

Lub sijhawm pib

3-15 vib nas this (adjustable nrog xws li)

5

Pib tam sim no

Ib -feem peb ntawm tag nrho -voltage start- nce kom txo tau qhov cuam tshuam ntawm daim phiaj hluav taws xob.

6

Tswj hom

Peb hom: tsis siv neeg, phau ntawv hluav taws xob, thiab phau ntawv qhia thaum muaj xwm txheej ceev.

7

Lub sijhawm ua haujlwm

Luv -lub sijhawm ua haujlwm (kev ua haujlwm tsis cuam tshuam rau kev tiv thaiv hluav taws nkaus xwb)

8

Kev tiv thaiv muaj nuj nqi

Overload, luv Circuit Court, theem poob, undervoltage, overvoltage, thiab theem kev ua yuam kev tiv thaiv.

9

Txoj kev sib txuas

Passive contact linkage ntawm hluav taws tswb tswj vaj huam sib luag, txuas hluav taws kub hydrant khawm, linkage ntawm lub siab hloov

10

Kev sib txuas lus muaj nuj nqi

Txheem RS485 interface, muaj peev xwm uploading kev ua haujlwm thiab teeb liab txhaum rau chav tswj hluav taws.

11

Kev tiv thaiv qib

IP30 (rau chav tsev twj tso kua mis)

12

Ib puag ncig ua haujlwm

Kub -10℃-+55 degree, av noo tsawg dua los yog sib npaug li 95% tsis muaj condensation

 

Core Structure thiab Functional Description

 

■ Lub hnub qub-Delta txo qis hluav taws xob pib qhov system (Core Starting Unit)

Lub txee tswj no txais yuavtus qauv hnub qub-delta txo voltage pib Circuit Court, muaj xws li lub ntsiab contactor, lub hnub qub pib contactor, delta khiav contactor, thermal overload relay, thiab lub sij hawm ncua sij hawm tswj chav tsev. Nws yog txoj kev nyiam pib rau nruab nrab thiab siab lub zog hluav taws xob twj tso kua mis thiab ua tau raws li qhov yuav tsum tau ua rau qis - cuam tshuam thiab siab - kev ntseeg tau pib ntawm cov twj tua hluav taws.

Txoj cai ua haujlwm: Nyob rau hauv thawj theem ntawm cov khoom pib, tus maub los tswj lub cev muaj zog windings ua haujlwm hauvlub hnub qub (Y) kev sib txuas, txo lub cev muaj zog davhlau ya nyob twg voltage mus rau 1/3 ntawm qhov ntsuas hluav taws xob, zoo heev txo qhov pib tam sim no thiab zam qhov cuam tshuam ntawm qhov pib loj tam sim no ntawm daim phiaj hluav taws xob, hlawv tawm cov kab thiab hloov khoom siv; tom qab lub cev muaj zog ceev stabilizes thiab pib ua tiav, nws cia li hloov mus raukev sib txuas ntawm delta (△) tom qab ncuakom khiav ntawm qhov nrawm thiab ntsuas lub peev xwm, xyuas kom meej tias cov twj tso kua dej mus txog qhov ntsuas lub taub hau thiab ntws tus nqi kom tau raws li qhov xav tau ntawm cov hluav taws tua hluav taws.

Cov txiaj ntsig tseem ceeb: Kev pib yooj yim-nce, qis tam sim no, qis qis tus nqi, kev ua haujlwm siab, tsis muaj teeb meem cuam tshuam txog kev cuam tshuam ntawm cov khoom pib muag muag, tsim nyog rau kev tiv thaiv hluav taws uas xav tau ntev - lub sij hawm standby thiab pib thaum muaj xwm ceev; qhov pib- lub sijhawm ncua sij hawm tuaj yeem hloov kho dawb los ntawm tus maub los kom hloov mus rau qhov pib- nce cov yam ntxwv ntawm cov twj tso kua dej nrog lub zog sib txawv.

 

■ Intelligent hluav taws tiv thaiv maub los (core control unit)

Lub txee yog nruab nrog lub siabntse tswj rau cov twj tua hluav taws, uas ua haujlwm tseem ceeb ntawm cov khoom siv lub hlwb. Nws cia li tswj lub twj tso kua mis pib-nce, kaw, hloov, tiv thaiv, thiab teeb liab kis tau tus mob thoob plaws tag nrho cov txheej txheem. Tsis zoo li cov tswj kev lag luam zoo tib yam, nws tau mob siab rau kev tua hluav taws- sib ntaus sib tua los tiv thaiv lub twj tso kua mis tsis siv neeg kaw thiab ua haujlwm tsis zoo, yog li ua tau raws li cov cai tswj kev nyab xeeb hluav taws yuav tsum tau ua.

Core nta:

1. Peb -hom ntse hloov: Nws muab peb hom kev ua haujlwm: tsis siv neeg, phau ntawv hluav taws xob, thiab phau ntawv ceev xwm txheej ceev. Kev hloov pauv hom yog cuam tshuam los tiv thaiv kev tsis sib haum xeeb thiab kev ua haujlwm tsis raug, thiab nws tsim nyog rau ntau yam xwm txheej xws li kev tshuaj xyuas txhua hnub, kev sib txuas tsis siv neeg, thiab hluav taws kub ceev.

2. Tag nrho tsis siv neeg hluav taws kub tswb linkage: Nws tuaj yeem tau txais cov teeb liab los ntawm lub tswb hluav taws kub tswj vaj huam sib luag, hluav taws kub hydrant nyees khawm, sprinkler siab hloov, ntws mus, thiab passive hloov. Thaum tau txais lub tswb ceeb toom hluav taws, nws cia li pib lub twj tua hluav taws kom ua tiav kev sib txuas ntawm kev tiv thaiv hluav taws.

3. Txhim kho kev tiv thaiv thiab kev nco: Tiag - lub sij hawm saib xyuas ntawm qhov ua tsis tau xws li fais fab theem poob, theem kev ua yuam kev, overload, luv Circuit Court, thiab lub cev muaj zog overheating. Thaum muaj kev txhaum tshwm sim, lub tshuab yuav nres tam sim ntawd, lub suab thiab lub teeb ceeb toom yuav qhib, thiab qhov txhaum cai yuav raug kaw. Nws muaj qhov ua tau - nyob rau hauv kev ua txhaum lub cim xeeb cia ua haujlwm los pab txhim kho kev ua haujlwm thiab kev saib xyuas kev daws teeb meem thiab tiv thaiv kev ua haujlwm tsis raug.

4. Tsis siv neeg tig ntawm lub ntsiab thiab thaub qabcov twj tso kua mis (yeem): Dual- cov qauv twj tso kua mis txhawb kev sib hloov tsis siv neeg ntawm lub ntsiab thiab cov twj tso kua mis thaub qab thiab hloov tsis siv neeg thaum tsis ua haujlwm. Thaum lub twj tso kua mis loj tsis ua haujlwm, lub twj tso kua mis thaub qab yuav pib khiav tam sim ntawd, ua kom cov dej tsis muaj kev cuam tshuam thoob plaws hauv cov txheej txheem.

5. Tej thaj chaw deb teeb liab upload: Tiag -lub sij hawm upload ntawm kev ua haujlwm, nres, ua txhaum, thiab phau ntawv qhia / tsis siv neeg cov xwm txheej teeb liab mus rau chav tswj hluav taws kom ua tiav cov chaw taws teeb saib xyuas thiab kev tswj hwm hauv nruab nrab.

6. Hluav taws kub- sib ntaus sib tua logic xauv : Lub twj tso kua mis raug txwv tsis pub nrestom qab hluav taws pib. Nws tsuas tuaj yeem hloov kho manually kom nres, uas ua raws li cov cai tiv thaiv hluav taws thiab tiv thaiv lub twj tso kua mis kom tsis txhob poob siab thaum sib ntaus sib tua.

 

■ Kev ceev ceev phau ntawv ua kom muaj zog (yuav tsum tau tiv thaiv hluav taws)

Cov khoom siv no nruj me ntsis ua raws li cov qauv kev lees paub hluav taws kub thiab yog nruab nrog ob lub zog pib thaum muaj xwm txheej ceev ntawmhluav taws xob phau ntawv thiab mechanical xwm ceev phau ntawv. Qhov no daws qhov phom sij tsis txaus ntseeg ntawm lub twj tso kua mis tsis ua haujlwm vim yog kev tswj tsis ua haujlwm, kev puas tsuaj thib ob, lossis teeb liab tsis ua haujlwm, thiab xyuas kom meej tias lub twj tso kua mis tuaj yeem pib 100% nyob rau hauv cov xwm txheej kub kub heev.

  • Vaj Huam Sib Luag Hluav Taws Xob Los Ntawm Txhais Tes Hom

Rau kev tshuaj xyuas niaj hnub thiab xwm txheej xwm txheej ceev, hloov lub pob qhov rooj ntawm lub vaj huam sib luag mus rau txoj haujlwm "phau ntawv" thiab ncaj qha tswj lub twj tso kua mis pib thiab nres ntawm lub vaj huam sib luag pib thiab nres khawm. Qhov no tso cai rau kev cuam tshuam ntawm cov cuab yeej ua haujlwm, ua rau nws tsim nyog rau kev debugging txhua hnub, kev tshuaj xyuas ib ntus, thiab kev daws teeb meem. Nws yooj yim rau kev khiav lag luam thiab muaj kev nyab xeeb thiab tswj tau.

  • Mechanical Emergency Manual Mode (Forced Emergency)

Qhov no yog qhov tseem ceeb tshaj plaws ua haujlwm kub ntxhov rau kev tiv thaiv hluav taws. Kev ywj pheej ntawm cov maub los thiab theem nrab tswj Circuit Court, nws muaj cov qauv siv tshuab ua kom huv, tsis tas yuav tsum muaj kev tswj hluav taws xob lossis cov teeb liab, thiab tsis cuam tshuam los ntawm cov khoom tsis ua haujlwm. Thaum lub tshuab hluav taws xob ntse hauv lub txee tswj tau kub hnyiab tawm, lub tshuab hluav taws xob thib ob ua haujlwm tsis zoo, PLC tsis ua haujlwm, lossis lub teeb liab chaw taws teeb tsis ua haujlwm, tab sis lub zog tseem ceeb yog qhov qub, cov neeg saib xyuas tuaj yeem siv lub tshuab ua haujlwm kub ntxhov ntawm lub txee.yuam kom kaw lub ntsiab Circuit Court contactor, hla lub hnub qub-delta qeeb pib theem thiab ncaj qha yuam kom pib lub twj tso kua mis ntawm qhov nrawm. Qhov no ua kom ntseeg tau cov dej kub ceev thaum muaj hluav taws kub thiab yog ib qho tseem ceeb, yuav tsum ua haujlwm rau kev kuaj xyuas hluav taws.

Qhov tseem ceeb ntawm kev ua haujlwm kub ntxhov: Mechanical Emergency manual > Electrical manual > Tsis siv neeg txuas

 

■ Zuag qhia tag nrho cov qauv thiab kev tiv thaiv tsim

Lub txee yog ua los ntawm thickened txias- dov steel phaj nrog electrostatic hmoov txheej, ua rau nws xeb- pov thawj, corrosion- tiv taus, ruaj khov, thiab ruaj khov. Internal Cheebtsam yog modularly nteg tawm, nrog lub ntsiab thiab tswj circuits wired nyias, cais cov muaj zog thiab tsis muaj zog tam sim no circuits, kom ntseeg tau zoo huv si thiab tshav kub dissipation. Cov cuab yeej tau nruab nrog lub hwj chim taw qhia teeb, lub teeb taw qhia khiav, lub suab tsis raug thiab pom lub tswb, thiab lub qhov rais hom zaub, muab cov ntsiab lus meej ntawm cov khoom siv. Cov hluav taws xob hluav taws xob tau nruab nrog ob qho tib si hluav taws xob thiab cov khoom siv sib cuam tshuam, tshem tawm cov kev pheej hmoo ntawm theem - mus rau -theem luv circuits tshwm sim los ntawm lub hnub qub -delta contactors, kom ntseeg tau tias muaj kev nyab xeeb siab heev.

 

Scope ntawm daim ntawv thov

 

1. Kev tswj cov twj siv hluav taws xob hauv tsev, cov twj tso kua dej tsis siv neeg, thiab cov twj tua hluav taws kub ruaj khov hauv ntau lub tsev;

2. Cov dej tua hluav taws rau cov chaw ua lag luam, cov tsev ua haujlwm, tsev kho mob, tsev kawm ntawv, cov zej zog, thiab cov chaw tsim khoom lag luam;

3. Hluav taws kub tswj cov tshuab uas xav tau lub hnub qub-delta txo-voltage pib, tsis siv neeg txuas, thiab cov twj tso kua mis thaum muaj xwm ceev;

4. Kev tsim kho tshiab lossis kho dua tshiab cov phiaj xwm tiv thaiv hluav taws uas ua tau raws li kev lees paub kev tiv thaiv hluav taws hauv lub tebchaws.

 

Installation thiab siv cov lus qhia

 

■ Kev Txhim Kho Ib puag ncig yuav tsum tau ua

1. Cov khoom siv tau muab tso rau hauv chav tsev twj tso kua mis, uas yog qhov zoo - cua tshuab, qhuav, tsis muaj plua plav, corrosive gases, thiab cov khoom tawg yooj yim thiab tawg;

2. Lub txee yuav tsum tau nruab ntsug rau hauv av, ruaj ruaj, nyob deb ntawm cov twj tso kua mis kev co, thiab muaj qhov chaw txaus rau kev saib xyuas.

3. Kev ntseeg siab hauv av nrog cov av tiv thaiv tsawg dua lossis sib npaug ntawm 4Ω ua kom cov khoom siv thiab cov neeg ua haujlwm muaj kev nyab xeeb;

4. Lub ambient kub yuav tsum tswj ntawm -10℃thiab +55℃. Kev teeb tsa sab nraum zoov yog txwv tsis pub raug los nag lossis tshav ntuj ncaj qha.

 

■ Kev teeb tsa thiab cov kauj ruam txuas

1. Ruaj ntseg cov khoom siv nyob rau hauv qhov chaw, ua kom tiav lub txee hauv av, thiab xyuas tias lub txee tsis muaj kev puas tsuaj, cov khoom tsis zoo, thiab cov xaim muaj kev ruaj ntseg;

2. Txuas mus rau peb lub-theem 380V lub ntsiab fais fab mov, paub qhov txawv ntawm cov xaim nyob, cov xaim nruab nrab, thiab cov xaim hauv av, thiab xyuas kom cov xaim txuas ruaj khov thiab ua kom zoo.

3. Txuas lub twj tso kua mis lub cev muaj zog load kab, nruj me ntsis raws li lub hnub qub -delta thaiv cov kev qhia tshwj xeeb rau cov hlua txuas, thiab tiv thaiv cov theem tsis raug thiab kev sib txuas xoob;

4. Txuas lub tswb hluav taws xob txuas hluav taws xob teeb liab kab, tawm tswv yim teeb liab kab, thiab RS485 kev sib txuas lus kab, kom ntseeg tau tias muaj kev sib txuas;

5. Ua ntej- fais fab- ntawm kev tshuaj xyuas: Paub meej tias txhua qhov hloov pauv nyob rau hauv txoj haujlwm qhib thiab tsis muaj qhov luv luv lossis qhov tsis raug hauv av hauv Circuit Court;

6. Fais fab rau thiab sim txhua theem kom ntseeg tau tias kev sib txuas tsis siv neeg, phau ntawv pib / nres ntawm hluav taws xob circuits, lub hnub qub -delta hloov, kev tiv thaiv kev ua txhaum, thiab txhua yam kev ua haujlwm kub ntxhov yog ib txwm muaj.

 

■ Cov txheej txheem ua haujlwm rau hom kev ua haujlwm

1. Tsis siv neeg hom (kev ua haujlwm niaj hnub)

Thaum lub qhov rooj vaj huam sib luag hloov mus rau txoj haujlwm "Automatic", cov khoom siv nyob rau hauv 24-teev hluav taws tiv thaiv lub luag haujlwm hom. Tom qab tau txais cov ntawv ceeb toom hluav taws los ntawm hluav taws kub tswj vaj huam sib luag, hloov siab, thiab khawm hluav taws tua hluav taws, nws cia li ua tiav lub hnub qub -delta txo lub siab pib, thiab lub twj tso kua mis tau muab tso rau hauv cov dej tua hluav taws; nyob rau hauv cov ntaub ntawv ntawm tsis ua hauj lwm, nws cia li tswb thiab cia li hloov ntawm lub ntsiab thiab backup twj, thiab tag nrho cov txheej txheem yog unattended.

2. Fais fab phau ntawv hom (kev tshuaj xyuas thiab commissioning hom)

Hloov lub vaj huam sib luag pob qhov rooj mus rau txoj hauj lwm "manual" kom lov tes taw tsis siv neeg txuas muaj nuj nqi. Manually tswj lub twj tso kua dej ua haujlwm ntawm lub pob pib / nres ntawm lub vaj huam sib luag. Qhov no tsuas yog rau kev tshuaj xyuas txhua hnub, kev kho cov khoom siv, thiab kho qhov tsis raug. Tsis txhob cia nws nyob rau hauv phau ntawv hom rau ncua sij hawm thaum lub sij hawm ib txwm ua hauj lwm.

3. Mechanical Emergency manual mode (mob kub ceev heev)

Siv tsuas yog thaum muaj hluav taws kub lossis hluav taws xob tswj qhov system tsis ua haujlwm. Qhib lub qhov rais ua haujlwm xwm txheej ceev ntawm lub txee, ua haujlwm rau cov neeg kho tshuab tshwj xeeb txhawm rau txhawm rau txhawm rau txhawm rau txhawm rau koom nrog, thiab ncaj qha pib lub twj tso kua dej ntawm qhov nrawm. Tom qab tua hluav taws, manually reset lub kov, disconnect lub hwj chim, thiab teeb meem thiab kho tej yam khoom malfunctions.Kev ua haujlwm tsis raug tso cai raug txwv nruj me ntsis hauv tsis yog - xwm txheej ceev.

 

Kev tu thiab tu

 

1. Kev tshuaj xyuas txhua hnub: Tshawb xyuas cov xwm txheej ntawm cov khoom siv hluav taws xob, kev ua haujlwm thiab qhov teeb meem txhaum cai txhua hnub kom paub meej tias cov khoom siv nyob rau hauv kev saib xyuas tsis siv neeg, tsis muaj lub tswb, tsis muaj suab nrov txawv txav thiab tsis muaj cua sov;

2. Kev saib xyuas txhua hli: Ua phau ntawv pib- nres kev xeem kom paub tseeb tias lub hnub qub -delta pib- hloov mus yog du thiab tsis muaj teeb meem, thiab lub tswb nrov thiab pom thiab lub teeb liab tawm tswv yim ua haujlwm zoo li qub; ceev cov hlua txuas thiab ntxuav cov plua plav hauv lub txee;

3. Kev tu txhua lub hlis twg: Ntsuas lub tswb hluav taws xob txuas ua haujlwm thiab lub ntsiab / standby twj tso kua mis hloov kev ua haujlwm, xyuas qhov tseeb ntawm theem poob thiab kev tiv thaiv overload, thiab xyuas qhov yooj ntawm cov khoom siv thaum muaj xwm txheej ceev;

4. Kev saib xyuas ib xyoos ib zaug: Kev ntsuam xyuas dav dav ntawm contactors, relays, controllers, thiab thermal relays; hloov cov khoom aging; thiab simulation ntawm kev lees txais hluav taws kev nyab xeeb kuaj los ntawm kev siv hluav taws xob rau tag nrho chav tsev.

5. Nws yog nruj me ntsis txwv tsis pub hloov cov kev pab cuam tswj, kho qhov kev tiv thaiv tsis, los yog luv luv - Circuit Court tiv thaiv yam tsis tau tso cai. Nws tseem raug txwv nruj rau cov uas tsis yog - cov kws tshaj lij los ua haujlwm rau cov khoom siv thaum muaj xwm ceev.

 

Troubleshooting Common Faults

 

Fault phenomenon

Ua txhaum

txoj kev ua

Pump tsis tuaj yeem pib hauv hom tsis siv neeg

Txuas lub teeb liab tsis txuas, xws li tsis muaj qhov txawv txav, txuas txuas txuas txuas ntxiv.

Tshawb xyuas lub tswb hluav taws xob hluav taws xob tswj hluav taws xob, rov pib dua cov tswj tsis tau, thiab kho qhov kev tswj hwm thib ob.

Lub twj tso kua dej pib- ua yuam kev, theem poob kev tiv thaiv

Peb -theem fais fab mov theem poob, xoob xaim, lub cev muaj zog winding txhaum, contactor contact puas.

Teeb meem cov khoom siv hluav taws xob tuaj, ceev cov terminals, kho lossis hloov cov contactor faulty, thiab kuaj lub cev muaj zog ua haujlwm.

Hnub qub-delta hloov pauv lag, pib ua haujlwm tsis ua haujlwm

Kev pib tsis tsim nyog- ncua sijhawm ncua sijhawm, lub hnub qub contactor tsis ua haujlwm, kev tiv tauj tsis zoo

Kho tus maub los pib qeeb, kho lossis hloov tus contactor faulty, thiab teeb meem cov xov hlau.

Overload tswb kaw

Cov dej twj tso kua mis dhau load, mechanical jamming, thiab tsis txaus thermal relay tsis.

Teeb meem kev ua haujlwm tsis zoo hauv lub twj tso kua mis dej, rov pib dua thiab kho qhov tsis zoo ntawm thermal relay.

Tus maub los tsis muaj zaub thiab tag nrho lub tshuab tsis ua haujlwm.

Cov khoom siv hluav taws xob puas, cua tshuab fuse, xws li malfunction

Hloov lub fuse tswj, kho lub hwj chim tswj, thiab tshuaj xyuas lossis hloov tus maub los.

 

Kev Tiv Thaiv Kev Nyab Xeeb

 

1. Kev teeb tsa, kev ua haujlwm, kev saib xyuas, thiab kev daws teeb meem yuav tsum tau ua los ntawm cov kws tshaj lij hluav taws xob thiab cov kws tshaj lij tiv thaiv hluav taws, thiab cov cai tswj kev nyab xeeb thiab kev tiv thaiv hluav taws yuav tsum tau ua raws li nruj me ntsis.

2. Thaum cov cuab yeej siv hluav taws xob, nws yog nruj me ntsis txwv tsis pub qhib lub hau thiab kov cov khoom nyob, thiab kev ua neej nyob thiab kev ua haujlwm txuas ntxiv raug txwv nruj;

3. Mechanical thaum muaj xwm ceev pib yog ib qho kev ua haujlwm rau cov hluav taws kub ceev. Nws raug txwv nruj heev kom ua haujlwm tsis tu ncua hauv lub neej txhua hnub kom tsis txhob muaj kev nyab xeeb kev nyab xeeb tshwm sim los ntawm kev sib tsoo pib- nce ntawm cov khoom hauv qab.

4. Cov twj tua hluav taws yog cov khoom siv tua hluav taws tshwj xeeb thiab yuav tsum tsis txhob siv rau lwm lub hom phiaj. Nws tseem raug txwv nruj kom kaw lossis kaw lub txee tswj tsis tau tso cai.

5. Thaum kho cov khoom siv, lub ntsiab fais fab yuav tsum raug txiav thiab ua hauj lwm yuav tsum tau ua tom qab lub Circuit Court yog kiag li de-energized los tiv thaiv hluav taws xob poob siab voltage.

6. Tsis tu ncua kuaj cov haujlwm xwm txheej ceev kom ntseeg tau tias cov cuab yeej tuaj yeem pib ntseeg tau txhua lub sijhawm thaum muaj hluav taws kub.

 

Khoom Warranty

 

Cov khoom no yog tsim thiab tshuaj xyuas nruj raws li lub teb chaws cov qauv kev tiv thaiv hluav taws thiab hluav taws xob specifications. Ua ntej tawm hauv lub Hoobkas, nws tau dhau los ntawm ntau qhov kev sim, suav nrog lub zog- ntawm kev sim, kev ntsuas kev sib txuas, kev ntsuas kev pib ua haujlwm, thiab kev ntsuas kev tiv thaiv, kom ntseeg tau tias nws ua tau raws li cov qauv zoo. Cov khoom muaj 18 lub hlis warranty. Thaum lub sij hawm warranty lub sij hawm, cov chaw tsim tshuaj paus yuav kho los yog hloov qhov chaw dawb xwb rau malfunctions tsis tshwm sim los ntawm tib neeg yuam kev los yog quab yuam majeure. Kev ua haujlwm tsis zoo tshwm sim los ntawm kev hloov pauv tsis raug cai, kev ua haujlwm tsis raug, kev puas tsuaj rau tib neeg, lossis kev siv txawv txav hauv ib puag ncig hnyav tsis muaj kev lav phib xaub.

 

Cim npe nrov: Hluav taws kub twj tso kua mis tswj txee, Tuam Tshoj hluav taws kub twj tso kua mis tswj txee manufacturers, lwm tus neeg, Hoobkas